Description
GENERATOR FEATURES:
- Standby rated
- Single step 100% load tested
- Wound 2/3 pitch for low harmonic distortion
- Class H insulation
- EPA CARB Tier 3 Compliant
- Automatic voltage regulation standard steady state voltage +/-1.5%
- Rubber engine & generator vibration isolation mounts. No need for isolation pads & extends the life of batteries & housing.
DSE 702 KEY START CONTROLLER:
Deep Sea digital genset controllers are highly advanced microprocessor controllers. Units come standard with simple key start controllers. Controllers are equipped with an hour meter, low oil and over speed and over temperature safety shutdowns.
ENGINE SPECIFICATIONS:
Make/Model: FPT Iveco N45 SM1
Type: Diesel
Governor: Mechanical
Cylinders: 4
Total Displacement: 4.5L
Aspiration: TurboCharged
Oil Filter Replacement: 600 Hours
Exhaust Outlet Size @ Muffler(ships loose): 3 Inches
Alternator: 90 amps
Starter: Bosch
Battery (Not Included): BCI 24 Minimum 650 CCA
ALTERNATOR SPECIFICATIONS:
Rating: (105/40°C) Standby
Type: 4 Pole-Revolving Field
Speed: 1800 RPM
Insulation System: Class H
Single Phase: 4 Lead
Three Phase: 12 Lead
Pitch: 2/3
THD: <5%
Coupling: Flexible Disc
Bearings (Maint Free): 1
Automatic Voltage Regulation: +/-1.5%
Single Phase Power Factor: 1.0
Three Phase Power Factor: 0.8
COMPRESSOR SPECIFICATIONS:
Type: Rotorcomp NK 31 Rotary
Horse Power: 10 HP
Oil Capacity: 101.4 oz (3.17 Qts)
Max Delivered Qty: 42 CFM
Max Operating Pressure: 218 PSI (15 BAR)
Max Outlet Temp: 230 °F (110 °C)
Max Ambient Temp: 115 °F(46 °C)
Cooling System: Oil to Air & Air to Air
Air Service Connection: 3/4" NPT
Units are set to operate at 40CFM @ 120PSI. See operators manual for adjustments and maintenance schedule.
OPERATIONAL DATA:
Output Voltage 60 Hz | kW | kVA | Amperes | |
120/240 1-PH | 40 | 40 | 167 | |
120/208 3-PH | 50 | 50 | 139 | |
120/240 3-PH | 50 | 50 | 125 | |
277/480 3-PH | 50 | 50 | 60 |
Consult factory for switchable voltage & 50Hz
Fuel Consumption
100% Load ................................................ 4.57 Gallons/Hr
50% Load .................................................. 2.72 Gallons/Hr
Derating Factors
Temperatures > 104°F .......................................... 3% per 10°F
Altitude ............................................................... 3% per 1000 ft
Prime Power ....................................................................... 10%
LIMITED WARRANTY:
WinPower warrants its product from material defects for a period of one year or unlimited hrs. Iveco warrants the engine for prime power generator applications for 1 year/ unlimited hours.